> UPS systems SOCOMEC > nergy storage systems SOCOMEC |
nergy storage systems SOCOMEC
Flywheel technology VSS+ DC (Voltage Support Solution)
APPLICATIONS
Backs up the DELPHYS UPS, overcoming the constraints, risks, costs and hazards of batteries. The solution inverter DELPHYS with dynamic storage of energy VSS+ DC was carried out by SOCOMEC UPS.
PRINCIPLE
VSS+ DC uses a very high-speed, rotating flywheel.The rotating assembly is held up by maintenance-free electromagnetic levitation, with no contact with other parts. A maintenance-free internal system vacuum eliminates friction and maximizes energy efficiency. The flywheel-driven generator supplies energy to the UPS during a power failure, thus providing continuous power to the load. When mains power is restored, the flywheel takes less than 5 minutes to return to full speed.
1. Containment housing
2. Composite carbon-fiber flywheel
3. Stator windings
4. Upper magnetic bearing
5. Vacuum system
6. Rotor
7. Lower magnetic bearing
ADVANTAGES
• Outstanding reliability : long service life (20 years)
• Extremely infrequent maintenance
• No vacuum pump maintenance
• Max. power in min. volume
• High efficiency > 99.8%
• Rapid recharging (5 minutes as standard)
• Virtually silent operation
• No load restrictions on ground
• Installation requiring no structural work
• Environmentally-friendly
THE VARIOUS CONFIGURATIONS Various solutions or combinations for meeting your requirements for electrical energy availability are possible depending on your operating constraints and technical environment.
1. short-duration POWER OUTAGES The VSS+ DC system is connected to the DC bus; it supplies the inverter when the low-voltage system exceeds the voltage tolerances. Thereby providing 99.5% protection against system failures.
2. working with a generator unit The VSS + DC supplies the inverter long enough for an emergency generator to take over the power supply and rapidly recharge the VSS + DC.
3. working with a battery When connected in parallel with a battery bank, the VSS+ DC cuts in during all short power failures and voltage sags; battery backup is used only for long duration cuts (or not at all if a backup generator is present). Battery life is extended by very infrequent demands.
4. working in parallel VSS+ DC units connected in parallel increase power and available backup time. No communications hardware or software needed, this capability is built-in.
DIMENSIONS
width |
height |
depth |
weight |
630 mm |
1800 mm |
830 mm |
590 kg |
TECHNICAL
|
* On 160 and 200 kVA versions, the power available depends on the DC voltage of the BUS to the UP