> UPS systems SOCOMEC > STS - Static transfer systems SOCOMEC

STS - Static transfer systems SOCOMEC

STATYS Rack

SOCOMEC UPS has more than 25 years of experience in designing, producing and customising Static Transfer Systems. A leader in multiple-source and multi bus architecture, SOCOMEC has installed thousands of STS systems (LTM) in many sectors that have demonstrated their adaptability and high reliability.
Investing more than 10% of turnover in R&D, SOCOMEC has always incorporated new technologies to ensure optimum quality and performance. STATYS, the latest design in STS incorporates the most advanced technologies combined with long experience to guarantee seamless and reliable power transfers.


ADVANTAGE

High reliability - Internal redundant design

Redundant microcontroller, SCR control, cooling and measurements, dual redundant supply.


Operational security & Ease of use

Designed to prevent human errors: clear display, signals and prevention systems.


Flexibility and adaptability to various types of applications


Compatible with every load (linear or non-linear with every Power factor and inrush current) and distribution system (single or three-phase, with or without neutral).

Remote data access in real time and from any location

Wide communication skills (LAN, email, serial, dry contacts, BMS) and upgradeable for future needs.

Compact design: saves up to 40% of valuable space

Compact Hot Swap 19” rack system (smallest on the market)

Full support and service

Real-time monitoring and maintenance services.


STATYS also provides protection against:
- main power source outage
- failures in the upstream power distribution
- operator errors.

TECHNICAL DATA

Size (A)

32 to 63

63 to 100

CHARACTERISTICS

Voltage (V)

 120 -127 / 220 - 240 / 254 (±20%)

 208 - 220 / 380 - 415 / 440 (±20%)

 

Number of phases

ph+N or ph-ph

(+ PE)

3ph+N or 3ph

(+ PE)

 

Frequency (Hz)

 50 or 60 (configurable ±5%)

 

Number of poles switching

2-pole switching

3 or 4-pole switching

 

Neutral system

Compatible with all earthing systems

 

Maintenance bypass

Interlocked and secured

 

Overload

120% for 60 minutes - 150% for 2 minutes

 

Efficiency

99%

 

Admissible power factor

No restrictions

 

DIMENSIONS AND WEIGHT

WxDxH [mm]

483 x 747 x 89

(19” x 747 x 2U)*

483 x 648 x 400

(19” x 648 x 9U)**

     

Weight [kg]

26

58

     

ENVIRONMENT

Operating ambient temperature

0 - 40 °C

   

Degree of protection

IP31

   

Relative humidity

 

 95 % 

       

Maximum altitude

1000 m a.s.l. without derating

   

Cooling 

 Forced ventilation

       

Sound pressure level

< 45 dB(A) 

   

STANDARDS

 

Performance and safety

IEC 62310, EN 50022, IEC 60364-4, IEC  60950, IEC  60529, IEC 60439-1

 Protection class

CB or PC class

EMC class

C2 category (IEC 62310-2)

* Depth does not include handles (+40 mm). Total height corresponds to 3U for fixed part and 6U for the Hot Swap module. - ** Depth does not include handles (+40 mm).






View all products »