> > VOLVO ENGINES SOCOMEC

Diesel genset FV 300 - Volvo engine

DIESEL GENSET - FV 300 with VOLVO engine


General information
Specifications

 

 

 

 

 

 

 

 

 

 

General Data
Standby Power L.T.P: 330 / 264 kVA / kW Prime Power P.R.P: 300 / 240 kVA / kW
Nominal Current: 433 Amps Nominal Voltage: 230/400 Volts
Frequency: 50 Hz


Engine
Make: VOLVO Penta Model: TAD1341GE
Emission Standard: Stage 2A Speed: 1500 RPM
Governor: electronic


Alternator
Make: SINCRO Model: SK250LL
Additional Data Canopied Set Open Set
Dimensions (L x W x H mm): 3946 x 1553 x 2286 3480 x 1300 x 2100
Weight (without fuel): 3630 kg 2940 kg
Fuel Tank Capacity: 500 Litres 500 Litres
Autonomy (100% load, full tank): 8 Hours 8 Hours
Noise Level: (LWA)
dB
dB

 

 

 

 

 

 

Front unit

Back aggregate

Line N
LTP kVA 330.0
LTP kW 264.0
PRP kVA 300.0
PRP kW 240.0
Hz 50
V 400
IP 23
Engine Volvo diesel
Generator Sincro
Turnover [r / min] 1500
Exhaust Emissions Stage II
Line N
Code generator with automatic FG NVS 300 AH
Code generator with manual control FG NVS 300 MH
Aggregate:
Maximum power LTP [kVA] 330.0
LTP Maximum Power [kW] 264.0
PRP Rated power [kVA] 300.0
PRP Rated power [kW] 240.0
Rated current [A] 433.0
Frequency [Hz] 50
Voltage [V] 400
Generator:
The manufacturer of the generator Sincro
Country of production Croatia
Type of generator SK250LL
Power generator (40 ° C, 1000m above sea level) [kVA] 300.0
Generator efficiency [%] 92.9
Voltage stabilization AVR Analog
The level of voltage stabilization [%] +/- 1
Protection [IP] 23
Insulation class H
Current harmonic distortion THD [%] <2.0
Reactance X''d [%] 8.9
Engine:
Engine Manufacturer Volvo
Country of production Sweden
Engine Type TAD1341GE
Net engine power [kW] 275.0
Turnover [r / min] 1500
Speed ​​control Electronic
The classification of G3
Engine capacity [l] 12.8
Number of cylinders 6
Installation of [V] 24
Cooling Volvo Coolant fluid VCS
The capacity of the cooling system [l] 44.0
Engine Oil Shell Rimula R4L
Oil capacity [l] 36.0
Exhaust Emissions Stage II
Type of fuel Diesel (EN 590)
Fuel consumption for the load of 75% [l / h] 47.9
The fuel consumption for 100% load [l / h] 62.5
Aggregate:
Fuel tank capacity [l] 500
Working time for a load of 100% [h] 8.0
The weight of the unit without the fuel [kg] 2940
Dimensions L x W x H [mm] 3480 x 1300 x 2100
Lion Guaranteed sound power level [dB] -
Explanation:
Rated power PRP ISO 8528 Specifies the maximum power available with varying load unit in continuous operation. Overload + 10% for up to 1 hour for every 12 hours of operation. Average power consumption within 24 hours should not exceed 70% of the PRP
Maximum power LTP ISO 8528 Specifies the maximum available power generator, with a limit up to 500 hours per year. Average power consumption within 24 hours should not exceed 80% of the LTP maximum uptime - 300h. No overload. Should be used in the event of a mains failure.
Disclaimer All parameters are given for reference conditions: ambient air temperature not higher than 40 ° C and a height of not more than 1000m above sea level
 
The controller 2025
Switch Controller
Main switch unit EATON LZM
Undervoltage coil (rudder. Manual) or upward (rudder. Automatic) the main switch
Beeper failure
Emergency stop button
Starting battery Ah 2x180
Battery charger (automatic control)
Motor heater with thermostat (rudder. Automatic)
Engine Oil Shell Rimula R4L
Low oil pressure control
Oil pressure
High engine temperature control
Motor temperature measurement
Electronic speed controller
The frame with the reservoir
Lockable fuel cap on the outside of the housing
Fuel level measurement
Fuel filter with water separator
Compensator and exhaust silencer supplied loose
Coolant Volvo Coolant fluid VCS
Wibroizolatory vibration motor and generator
Handles loading
Manual oil drain pump
Heater switch on the front panel
Bath Retention
Leakage sensor in the hot water storage
Custom fuel tank capacity
Battery disconnect switch
Receiving full power socket
Security slot (as agreed)
Residual current protection
ATS system
GPRS communication card
Ethernet communication card
Connecting the unit with the launch
 
 
AMF controller 25
The AMF (automatic switching in case of power failure)
Generator voltage measurement - Phase 3
Measuring voltage - Phase 3
Current measurement - 3 phase overcurrent protection IDMT
Measurement kW
KVA Measurement
Measuring kWh
Generator protection
Alarm signaling
A complete history
Event History
Real-time clock with battery
Confirmation MCB control position
Confirmation GCB control position
Checking the battery charge
Engine Hours
Remote obługa using SCADA software

 

 

For individual orders can be applied in the unit selected driver from the company's offer Deep Sea Electronics, having CAN J1939 interface.

 

Aggregate

Name Date added Version Size Downloads
Sheet 06-03-2014 Version: 3 489.46 KB 1376
Manual EN / DE / RU 06-04-2014 Version: 141115 2.44 MB 1804
General Operating Instructions unit 11-03-2014 Version: 141115 2.51 MB 1755
The foundation and the foundation for unit selection 08-03-2014 Version: 1 267.86 KB 186

Drivers

ComAp MRS / AMF - Fact Sheet 18-12-2013
2.44 MB 1512

Generators

Sincro - Fact Sheet 03-09-2013
1.04 MB 1849
Sincro generator SK 250 - Sheet 08-10-2013
1.45 MB 1689

Engines

Volvo Penta - Fact Sheet 10-09-2013
220.11 KB 1670
Volvo Engine TAD1341GE - Sheet 08-10-2013
226.51 KB 1359

Switches

EATON LZM - Fact Sheet 19-11-2013
969.81 KB 1919

Installation of the unit

Built aggregate Fogo - flowchart







You may be interested in


Become a partner of

DTS